Software Manual 128
Automation Tab
The user interfaces will have the ability to:
Configure/Display local station information such as station name and station number.
Configure/Display serial ports
Configure/Display remote stations
Configure/Display I/O transfers
Configure/Display MODBUS forward stations
Configure/Display MODBUS registers allocation
3.6.1 Local Station
Click on the Local Station sub menu item and the following menu will appear:
Enable Modbus: Select Yes to enable the Modbus option.
Station Name (Required): Enter the name of the local station. The station name must be less than or equal to 32 char-
acters.
Sation Number (Required): Enter the local station number. The station number must be in a range of 1 - 247. The val-
ues may be duplicated for other station as long as the station as long as the station can be uniquely addressed by an IP
address or is connected on a serial port. Note: 0 is a broadcast address. 248-255 are reserved addresses.
Modbus Local Port (Required): Enter a valid port number. The port must be within the range of 1 - 65535 and the rec-
ommended default port is set to 502. Take care to choose a port number not already used by other system services.
Consult Status
Network Socket Statuses TCP Only for a list of ports currently in use. Please note that a Firewall
Allow rule will need to be added for remote access.
Click SAVE to store the settings for the next reboot, or click APPLY for the settings to take effect immediately.